Command bit Command
0 Setting tare value of a weighing platform
1 Setting the value of LO limit of a weighing platform
2 Setting outputs status
3 Setting the value of MIN threshold
4 Setting the value of MAX threshold
Notice:
A complex command requires setting an appropriate parameter
(addresses from 4 to 48. – see table “List of parameters in a complex
command”).
Example:
0000 0000 0000 0010 – a command carries out setting of the LO limit
for a value given in parameter LO (address 10 – see table “List of
parameters in a complex command”).
• Platform – complex command parameter: number of a weighing platform.
• Tare – complex command parameter: tare value (in an adjustment unit).
• LO – complex command parameter: the value of LO limit (in an
adjustment unit).
• Outputs status – complex command parameter: determines outputs
status of an indicator.
Output no. 12 11 10 9 8 7 6 5 4 3 2 1
OFF 0 0 0 0 0 0 0 0 0 0 0 0
ON 1 1 1 1 1 1 1 1 1 1 1 1
Example:
Mask of active outputs 2 and 4: 0000 0000 0000 1010
• MIN - complex command parameter: the value of MIN threshold
(in a measuring unit of an enabled working mode).
• MAX - complex command parameter: the value of MAX threshold
(in a measuring unit of an enabled working mode).