EasyManuals Logo

SBC PCD2 Series User Manual

SBC PCD2 Series
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-57
I/O modules PCD1|PCD2
PCD2.W11x
5
Technical data for add-on modules (variant modules)
PCD2.W110 4 inputs for Pt 100 probes
Current sources 2 mA
Measuringrange  -50°C … +150°C
Accuracy of measurement better than 0.2 °C
PCD2.W111 4 inputs for Ni 100 probes
Current sources 2 mA
Measuringrange -50°C … +150°C
Accuracy of measurement better than 0.4 °C
PCD2.W112 4 inputs for Pt 1000 probes
Current sources 0.2 mA
Measuringrange  -50°C … +150°C
Accuracy of measurement better than 0.2 °C
PCD2.W113 4 inputs for Ni 1000 probes
Current sources 0.2 mA
Measuringrange - -50°C … +150°C
Accuracy of measurement better than 0.4 °C
PCD2.W114 4 inputs for Pt 100 probes
Current sources 0.2 mA
Measuringrange  0°C … +350°C
Accuracy of measurement better than 0.4 °C
Accuracy of measurements
The curves below show the maximum measurement error
(measurement and repeating accuracy).
Total error = linearization error + repeating error
Each channel is calibrated to the minimum and maximum values:
-50 °C → 0 + 2 LSB
+150 °C → 4095 - 2 LSB
For these two values, the measurement error = 0.

Table of Contents