Digital input/ output parameter group 03
PARAMETER DESCRIPTION 90
Parameter
Name
Default
Setting Range
Content
03-00
P.83
Terminal STF
input function
0
39
STF/STR +STOP (Use with RUN signal, when ON, motor
runs reverse, when OFF, motor stops then runs forward.)
40
P_MRS (Stops inverter output immediately by pulse signal
input)
41~42
Reserved
43
RUN_EN (Enable digital input terminal operation)
44
PID_OFF (Enable digital input terminal turning off PID)
45
Second frequency command source mode
46~91
Reserved
92
Fire mode command 1( RUN command included)
93
Fire mode command 2( RUN command excluded)
03-01
P.84
Terminal STR
input function
1
Same as 03-00
Same as 03-00
03-03
P.80
Terminal M0 input
function
2
Same as 03-00
Same as 03-00
03-04
P.81
Terminal M1 input
function
3
Same as 03-00
Same as 03-00
Digital input terminals function selection
In default, 03-03(P.80)=2RL), 03-04(P.81)=3RM), 03-00(P.83)=0STF), 03-01(P.84)=1STR.
Changing terminal input function values change the function of the terminals. For example, 03-03(P.80)=2 means
that M0 terminal acts as RL. If 03-03(P.80) is set to 8, M0 terminal function will change to RT, which will act as
“second function”. Another example, 03-00(P.83)=0 means that STF terminal serves as “inverter runs forward”
function, and if change 03-00(P.83) to 6, STF terminal function will change to OH, which will serve as the input
terminal of external thermal relay
Set value:6 OH(External thermal relay):
Old motors usually come with thermal relay attached to the front of the motor to prevent motor from overheating.
When external thermal relay actuate, inverter will alarm and show “OHT” on keypad.
Four different wiring techniques (1 means ON, 0 means Off, and X = 0134
1) Two-wire control mode 1:
K0
K1
STF(03-0X(P.8X)=0)
STR(03-0X(P.8X)=1)
SD
K0 K1
Run
command
0
1
0
1
11
0
0
Stop
Forward
Reverse
Stop
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SC3 Series and is the answer not in the manual?

Shihlin electric SC3 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSC3 Series
CategoryInverter
LanguageEnglish

Related product manuals