Digital input/ output parameter group 03
PARAMETER DESCRIPTION 92
Set value : 45 Second frequency source mode
When this terminal is on, target frequency is set by 00-17(P.97).
Fire mode command 1(RUN command included)
When in fire mode(06-84(P.207) = XXX1 or XXX2), if the terminal with related function is ON, the inverter goes into
fire mode and starts compulsorily.
Fire mode command 2(RUN command excluded)
When in fire mode (06-84(P.207) = XXX1 or XXX2), if the terminal with related function is ON, the inverter goes
into fire mode.
When the inverter stopped, if the terminal with related function is ON, the inverter goes into fire mode, but not in
running status.
When the inverter is in running status, if the terminal with related function is ON, the inverter runs base on the set
parameter.