System Components and Technical Data
100 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Substation
Serial communication protocol according to IEC60870-5-101
UMPST0 is substation
Unbalanced transmission Slave
Network configuration
Multipoint-partyline
Multipoint-star
Max. connections: 1
System or device (application function)
Controlled station
Physical layer / data flow control
Unbalanced interchange circuit according to V.24/V.28 standard
Transmission medium (half duplex)
Byte Frame (8E1)
Interoperability according to IEC 60870-5-101 Ed.1
Interoperability according to the following document:
SICAM RTUs Interoperability IEC 60870-5-101/104 (DC0-013-2)
Acquisition of events (transmission of data ready to be sent)
General interrogation, outstation interrogation
Non Interruptible GI
Send GI-data as class 1 data
Convert general interrogation command in receive direction to Broadcast
Clock synchronization according to IEC 60870-5-101
Clock synchronization with <TI:=103> clock synchronization command
Acquisition of transmission delay (secondary station) used for correction of clock syn-
chronization with <TI:=106>
Correction of clock synchronization (via parameter)
Accuracy +/-20ms
Accuracy (relay operation) +/-20ms
*)
File transfer
Optimized parameters for selected transmission facilities (modems)
Predefined optimized parameters for selected transmission facilities
Free definable parameters for transmission facility
5 V power supply for external modem
ATTENTION: check power consumption of external modem!
Data transmission in relay operation mode (multi-point traffic with routing)
Protocol element control and return information
Protocol element control messages
Send (general) interrogation command to all
I bit handling for time ON/OFF
Protocol element return information
Status DTR (1 = state line active)
Status DSR (1 = state line active)