Use Cases
592 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
E.5 Usage with Static Routes
E.5.1 General
Static routing is based on a fixed definition of the path of data packages between two end sys-
tems. This definition is written down by administrators in a routing table. This kind of routing
serves for security, respectively is used in network configurations, if several default gateways
are used.
Because of the big effort for the manual maintaining of the tables the number of routes is re-
stricted.
Number of static routes: 10
Parameter of static routes:
Source IP address
Destination IP address
Gateway IP address
Subnet mask
Interfaces: X1, X4
E.5.2 Configuration
Activation of the „static routes“
Parameter Network settings | IP address | advanced parameters | Enable
static routes = YES.
Definition of the routing table
Parameter Network settings | IP address | advanced parameters | static
routes = Number of lines x (max. 10).
Mode of the Ethernet Ports
Parameter Network settings | IP address | Mode of ethernet ports = 1 IP ad-
dress (connected ports in switch mode):
The data packages are sent via the interfaces X1 and X4.
Parameter Network settings | IP address | Mode of ethernet ports = 2 IP ad-
dresses (independent ports):
The data packages are sent via that interface (X1 or X4) to which the respective source IP
address (Own IP address X0 or Own IP address X1) is assigned.