System Overview
46 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
2.1.5.4 Configuration Rules for I/O Modules
With use of external I/O Modules please pay attention to the following rules.
General
The total power of all modules must not exceed the available power of the power supply
module
The total power of the external I/O Modules must not exceed the following values:
CP-8000: 5 W
CP-802x: 7 W (PS-862x), 8 W (PS-864x)
(when using the fiberoptical interface CM-0847, 1 W is less available)
I/O Modules with a power consumption >800 mW must be mounted as of the first slot
Maximal 2 AO modules possible, with 2-line arrangement only in the first line permitted
Mixing of current and voltage on the same AI module is not possible
Mixing of binary information and pulse commands on the same DO module is not possible,
except with usage of the categories DO_SX and DO_DX (for details refer to manual
SICAM RTUs Common Functions Peripheral Elements According to IEC 60870-5-
101/104, chapter "Binary Information and Command Output"
Mixing of signals on one module DO-820x or DO-821x:
Mixing of DO_SX, DO_DX, DO_SC_1.5POL and DO_DC_1.5POL possible
Mixing of DO_SC_1POL and DO_DC_1POL possible
Mixing of DO_SC_2POL and DO_DC_2POL possible
Mixing of DO_SX and/or DO_DX with DO_SC_1POL and/or DO_DC_1POL not possi-
ble
With use of AI-8510 (with current measurement), for each module a CM-8820 must be
equipped; the modules CM-8820 must be always equipped at the end of a module line or
at a separate line
Option “Assignment of Return Information to Pulse Command”
With the parameter-settable assignment the sequence of DI modules and DO modules is
arbitrary
With the fixed assignment respectively after a DI-811x (DI-610x) a DO-821x (DO-62xx)
must be equipped
For further details refer to section 9.1.11.5.5, Command Output.
Option “Checked Command Output” (applies for CP-8000 with SICAM TM I/O Modules)
Only 1 command output basic module may be connected, alternatively
DO-6220, command output according to IC1
DO-6221, command output according to RC1
The command output via DO-6220 or DO-6221 without a DO-6230 is not possible
Up to 7 command output relay modules DO-6230 may be connected
The command output via DO-6230 without a DO-6220 or DO-6221 is not possible
On a DO-6230 either 1-, or 1.5- or 2-pole impulse commands can be assigned (mixture on
the same module is not permitted)
Additionally, further DO module types can be used
For further details refer to section 9.1.11.5.5, Command Output.