General Information
34 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
1.1.7 Data Storage on SD Card
With the engineering, all data of a device – such as firmware and parameters – are stored
centrally on an exchangeable SD card in a non-volatile manner.
Upon startup of the device, all required data is checked and is - in case of differences to the
device settings - automatically transferred from the SD card. The transfer only occurs in case
of valid firmware and parameter signatures. Thus, when the device is exchanged with the
same type, no subsequent loading process, this means, no engineering tool, will be required.
The configuration is transferred directly to the replacement device (plug and play).
1.1.8 Compatibility
CP-8000/CP-802x is in the range of IEC 60870-5-101/103/104, when using standard proto-
cols, compatible with the hitherto existing SICAM RTUs system family (SICAM AK,
SICAM TM, SICAM EMIC, SICAM MIC, SICAM BC).