System Components and Technical Data
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 111
DC8-037-2.02, Edition 10.2017
5.5.5 ET84
5.5.5.1 Functions
LAN/WAN communication over Ethernet TCP/IP - general
10 Mbit/s (full duplex)
1)
10 Mbit/s (half duplex)
1)
10 Mbit/s (full duplex , auto negotiation)
1)
10 Mbit/s (half duplex, auto negotiation)
1)
10/100 Mbit/s (half duplex / full duplex, auto negotiation)
1)
100 Mbit/s (full duplex)
1)
100 Mbit/s (half duplex)
1)
100 Mbit/s (full duplex, auto negotiation)
1)
100 Mbit/s (half duplex, auto negotiation)
1)
Auto-MDIX (Auto Medium Dependent Interface Crossover)
1)
Parameters for TCP/IP optimization
1)
TCP/IP Keep Alive
1)
LAN/WAN communication over Ethernet TCP/IP according to IEC 60870-5-104
Controlled station
Controlling Station
Max. connections: 100
2)
Supported Ports
Port 2404: IEC 60870-5-104
Port 80: HTTP (Hypertext Transfer Protocol) - “Remote operation for SICAM
TOOLBOX II“
1)
Port 443: HTTPS (Hypertext Transfer Protocol over SSL/TLS) - “Remote operation for
SICAM TOOLBOX II“
1)
Port 123: NTP V3 (Network Time Protocol)
1)
Port 123: SNTP V3 (Simple Network Time Protocol)
1)
Special protocols:
Address Resolution Protocol (Gratuitous ARP)
1)
Interoperability according to the following document:
SICAM RTUs Interoperability IEC 60870-5-101/104 (DC0-013-2)
Acquisition of events (transmission of data ready to be sent)
General interrogation, outstation interrogation
Clock synchronization according to NTP (Network Time Protocol)
NTP server
1)
NTP client
1)
SNTP client
1)
Command transmission
Command transfer monitoring (dwell time monitoring)
Set control location
Check control location
Transmission of integrated totals
Protocol element control and return information
Protocol element control message
Send (general) interrogation command
Preset control location
Protocol element return information
PRE return information 0 “Status DATA TRANSFER (Master Module)”
PRE return information 1 “Status DATA TRANSFER (104)