System Components and Technical Data
160 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.3.6 DO-6200
5.7.3.6.1 Functions
Pulse commands
t1
Output of pulse commands
1-pole
Single, double and regulating step commands
Command output (OC)
Application functions and procedures according to IEC 60870-5-101/104
Formal check
Direct command
Select and execute command ("select/execute")
Retry suppression
1-out-of-n check
Control location check
Command locking
Synchronization
Revision
Command output time
Settable
Dependent on the process
Return information monitoring
Command prolongation
Switching sequences
Command output for the auto-reclose function
If outputs of the module are used for pulse commands, no outputs of the same module
can be used for binary information output
Binary information output
Selectable behavior on communication failure
ta
(deactivation or retention)
Deactivation on module failure
ta
Spontaneous transmission
t
or
Periodical transmission
a
If outputs of the module are used for binary information output, no outputs of the same
module can be used for pulse commands
Usage of outputs as Watchdog
Return information to pulse command assignment
Settable assignment for messages and pulse commands, which are acquired or output
on the I/O Master Module
Predefined assignment for messages and pulse commands, which are acquired or
output on the I/O Master Module