System Components and Technical Data
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 145
DC8-037-2.02, Edition 10.2017
5.7.1.2 DO-8203
5.7.1.2.1 Functions
Pulse commands
t1
Checked output of pulse commands
1-pole, -pole, 2-pole
Cannot be mixed
Single, double and regulating step commands
Command output (OC)
Application functions and procedures according to IEC 60870-5-101/104
Formal check
Direct command
Select and execute command
Retry suppression
1-out-of-n check
Control location check
Command locking
Synchronization
Revision
Command output time
Settable
Dependent on the process
Return information monitoring
Command prolongation
Switching sequences
Command output for the auto-reclose function
If outputs are used for pulse commands, no outputs can be used for binary information
output
Binary information output
Selectable behavior on communication failure
ta
(deactivation or retention)
Deactivation on module failure
ta
Spontaneous transmission
t
or
Periodical transmission
a
If outputs are used for binary information output, no outputs can be used for pulse
commands
Usage of outputs as Watchdog
Binary information and command output
Settable output of the categories DO_EX and DO_DX
Mixed output of binary information items and commands on 1 DO module possible
Output of persisting commands