Ambient Conditions
80 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
4.4.2 Power Supply
Parameter Value Test standard Product standard Class
Dielectrical test (50 Hz)
U DC 70 V/AC 33 V
3.0 kV
eff
60 s IEC 61010-1 IEC 61010-1
VW3
Dielectrical test (50 Hz)
DC 70 V/AC 33 V U
DC 286 V/AC 253 V
(220 VDC+30%/230 VAC+10%)
3.0 kV
eff
60 s
3.8 kV
eff
5 s
IEC 61010-1 IEC 61010-1
VW3
Impulse voltage 1.2/50 µs
common
5.0 kVp IEC 60255-27 IEC 60870-2-1 VW3
Impulse voltage 1.2/50 µs
normal
5.0 kVp IEC 60255-27 IEC 60870-2-1 VW3
Voltage tolerance DC +30/-25% IEC 60870-2-1
IEC 60654-2
DC3
DC4
Voltage tolerance AC +10/-15% IEC 60870-2-1
IEC 60654-2
AC2
AC3
Starting current Klasse S1 IEC 60870-4
Fast transient burst
common
4.0 kVs 5 kHz IEC 61000-4-4 IEC 60870-2-1 4
Fast transient burst (fast
repitition)
4.0 kVp 100 kHz IEC 61000-4-4
Fast transient burst
common
4.0 kV IEEE C37.90.1
Fast transient burst
transverse
4.0 kV IEEE C37.90.1
Surge 1.2/50 µs
common
4.0 kVp IEC 61000-4-5 IEC 60870-2-1 4
Surge 1.2/50 µs
normal
4.0 kVp IEC 61000-4-5 IEC 60870-2-1 >4
Induced HF voltage 10 V 0.15…80 MHz
80% AM 1 kHz
IEC 61000-4-6 IEC 60870-2-1 3
Voltage dips, short-time
interruption and voltage
fluctuations on AC input
connections
Einbrüche: (U
N
)
20% 5s
30% 20ms
30% 500ms
40% 200ms
60% 200ms
60% 1s
70% 500ms
Unterbrechungen:
(∆U
N
)
100% 10ms
100% 20ms
100% 50ms
100% 100ms
100% 1s
100% 5s
Schwankungen: (U
N
)
±8% 5s
IEC 61000-4-11 IEC 60870-2-1
IEC 61850-3 Ed.2
Frequency fluctuations AC 10% IEC 61000-4-11 IEC 60870-2-1 >F3
Ring waves 100 kHz
common
2.0 kVp IEC 61000-4-12 IEC 60870-2-1 3