System Components and Technical Data
116 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Common Functions IEC 61850 Server
LAN/WAN communication over Ethernet TCP/IP - general
100 Mbit/s (full duplex, auto negotiation)
1)
IEC 61850 server
Edition 2
GOOSE
2)
Max. number of servers (max. connections): 6
Max. number of “logical devices” (including all servers): 300
Max. number of “logical nodes” (including all servers):
3)
Max. number of data points:
4)
ACSI services
5)
Common data classes
5)
Attributes
5)
Supported functionality according to:
PICS (Protocol Implementation Conformance Statement)
PIXIT (Protocol Implementation Extra Information)
Supported Logical Nodes and their Attributes
Supported ports
Port 102: MMS (Manufacturing Message Specification)
Port 80: HTTP (Hypertext Transfer Protocol) - “Web server
1)
Port 80: HTTP (Hypertext Transfer Protocol) - “Remote operation for
SICAM TOOLBOX II“
1)
Port 443: HTTPS (Hypertext Transfer Protocol over SSL/TLS) - Web server“
1)
Port 443: HTTPS (Hypertext Transfer Protocol over SSL/TLS) - “Remote operation for
SICAM TOOLBOX II“
1)
Port 123: NTP V3 (Network Time Protocol)
1)
Port 123: SNTP V3 (Simple Network Time Protocol)
1)
Acquisition of events
Static data sets
Buffered reports
Unbuffered reports
Transmission of files
Disturbance records to SICAM DISTO
Transmission of integrated totals
General interrogation
Command transmission
Direct control with normal security
Direct control with enhanced security
SBO control with enhanced security
Setting groups
Clock synchronization according to NTP (Network Time Protocol)
NTP server
1)
NTP client
1)
SNTP client
1)
Functions for the support of redundant communication routes
Server redundancy
GOOSE redundancy
Protocol element control and return information
Protocol element control message
Send (general) interrogation command
SICAM TOOLBOX II connection over LAN/WAN ("remote connection")
Remote connection based on HTTP/HTTPS
Authentication in SICAM RTUs using connection password (optional)
Warning “Remote Connection”