System Components and Technical Data
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 123
DC8-037-2.02, Edition 10.2017
Special Functions
SICAM FCM “parameter loading“ (SICAM FCM V2.00, V2.10, V2.20, V2.30)
SICAM FCM “firmware loading“ (SICAM FCM >=V2.00)
Engineering
TOOLBOX II + OPM
Web engineering
___
1)
this specification refers to the max. number of possible stations for MODBUS Master in SICAM
RTUs (per communication interface); due to performance and required response time, in most cas-
es only a few stations are possible (typ. 20-30); the MODBUS protocol itself defines a max. possible
number of 247 stations per line
2)
broadcast addressing is only restricted supported by Master
3)
external converters (V.24/V.28 V.11) are required in some cases
Substation
Serial communication according to Modicon MODBUS
MODST0 is substation
MODBUS protocol half duplex link transmission procedure
MODBUS RTU-Mode
MODBUS ASCII-Mode
Max. connections: 1
1)
Message protection
CRC16 + parity (optional) “RTU-Mode“
LRC + parity (optional) “ASCII-Mode
Network Configurations
Point-to-point
Multiple point-to-point (extra interface required for each point-to-point configuration)
Multipoint-partyline
Multipoint-star
Data concentrator
MODBUS Slave address 0 “broadcast“
MODBUS Slave addresses 1…247
Physical interface
RS-232 - unbalanced interface according V.24/V.28 standard
RS-485 - balanced interface according V.11 standard
2)
RS-422 - balanced interface according V.11 standard
2)
Transmission line (half duplex)
Interoperability according to the following documents:
SICAM RTUs MODBUS Interoperability (DC0-073-2)
Clock synchronization for selected MODBUS Slave devices
Clock synchronization for OMV
Optimized parameters for selected transmission facilities (modems)
Predefined optimized parameters for selected transmission facilities
Free definable parameters for transmission facility
5 V power supply for external modem
ATTENTION: check power consumption of external modem!