Engineering via SICAM WEB
334 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
After the startup the configured I/O Modules appear in the directory tree under
SICAM A8000 CP-80xx | Master module | I/O Master module | <0…7>: <I/O module name>.
You find more detailed information on the I/O Modules in the manuals
SICAM RTUs
Ÿ
SICAM I/O Modules and SICAM RTUs
Ÿ
SICAM TM I/O Modules.
Please pay attention to the configuration notes and rules for the equipment of I/O Modules in
section 2.1.5, I/O Modules.
Note
The detected configuration is checked with each additional startup against the actually connected
I/O Modules. With deviation the target device notifies an error.
If the once detected configuration is changed, pay attention to section 11.4.3, Adapt New Equipped I/O
Modules in the Parameterization.