Engineering via SICAM WEB
374 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
Flutt_t_stable Flutter suppression: stability time in seconds.
0 = stability time defined through parameter
Flutt_t (S)
0.1 to 6553.5
DI_SI – single-point
information input
Inversion Inversion (S)
NO/YES
block Blocking (= not used) (S)
NO/YES
Flutt_dp_qds Datapoint quality discriptor for fluttery binary
information
BL/IV
input function Functionality of the binary input. This parame-
terization permits to disable the information
input for revision handling.
SVM_monitoring Power monitoring. The sensor voltage is
monitored by an own power monitoring input
(S).
NO/YES
Flutt_Number Number of transients for flutter suppression
(S)
SW_Filter_t Software filter-time in s (S)
Flutt_t Flutter time in seconds.
0 = no fluttersuppression (S)
0.1 to 6553.5
State_of_flutter_information Information state in message with BL bit
Delay_t Delaytime from ON singlepoint information in
seconds
0 to 16000
Moduleselection_SVM_
monitoring
Switch for power monitoring handling (PM)
Standard PM (P
M inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI module.
Flutt_t_stable Flutter suppression: stability time in seconds.
0 = stability time defined through parameter
Flutt_t (S)
0.1 to 6553.5
DI_CV – count pulse
acquisition
message_blocking_t Message blocking time in seconds. During this
time period, identical messages will be dis-
carded without error information.
0.1 to 6553.5
interval_time_0 Interval time. As transmission trigger or latch
trigger of the counts it is also possible to set
an interval. The belonging time is to configure
here.
interval_time_1 Interval time. As transmission trigger or latch
trigger of the counts it is also possible to set
an interval. The belonging time is to configure
here.
Inversion Inversion (S)
NO/YES
block Blocking (= not used) (S)
NO/YES
Type Conditioned value type (S)