Engineering via SICAM WEB
382 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
select_execute_t Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0 to 6553.5
RS_Image_CASDU1 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_CASDU2 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA1 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA2 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_IOA3 Address of corresponding return state infor-
mation (S)
0 to 255
RS_Image_TI Type identifier of corresponding return state
information (S)
• Single-point information
• D.-point information
Term_with_Conf Sending of termination immediately after
sending of confirmation (S)
NO/YES
Output_t_0 Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
termination_t_0 Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
RS_react_t_0 Information reaction time (S)
Pulse command: 0 .. time appropriate to
output time
Persistent command: 0 .. time appropriate to
termination time
0 to 6553.5
Output_t_1 Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
termination_t_1 Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
RS_react_t_1 Information reaction time (S)
Pulse command: 0 .. time appropriate to
output time
Persistent command: 0 .. time appropriate to
termination time
0 to 6553.5