Engineering via SICAM WEB
444 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Switch off Test Mode
Precondition: The application program is in the test mode.
If you click on the button , the test mode will be terminated.
The status changes as follows:
Cold Start
When pressing the button (Cold start), the following dialog is opened:
You have the possibility to abort the procedure.
Click on the button in order to perform a cold start
The test mode is switched on and the values of all variables are initialized with 0 and the ap-
plication program is restarted. The program parts PLC_RESET and PLC_INIT are processed
once and if the program has been previously
in the State: running, the program part PLC_START is processed cyclically again
in the State: halt, the program processing is halted
Warm Start
When pressing the button (Warm start), the following dialog is opened:
You have the possibility to abort the procedure.
Click on the button in order to perform a warm restart
The test mode is switched on and the values of the volatile variables are initialized with 0 and
the application program is restarted. The program parts PLC_RESET and PLC_INIT are pro-
cessed once and if the program has been previously
in the State: running, the program part PLC_START is processed cyclically again
in the State: halt, the program processing is halted