System Overview
48 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
The protocols are available via the respective interfaces at the Master Module.
Firmware Protocol name
CP-8000 CP-8021 CP-8022
LAN
RS-232
RS-485
LAN
RS-232
RS-485
LAN
RS-232
RS-485
GPRS
Integrated standard protocols
CPC80 Remote operation X1, X4 X2 X1, X4 X2 X1, X4 X2 X7
CPC80 SNMP X1, X4 X1, X4 X1, X4 X7
CPC80 SysLog client X1, X4 X1, X4 X1, X4 X7
CPC80 NTP/SNTP X1, X4 X1, X4 X1, X4 X7
CPC80 RADIUS X1, X4 X1, X4 X1, X4 X7
Equipable standard protocols
103MT0 IEC 60870-5-103 Master X2 X3 X2 X3 X2, X6 X3, X6
BPPT0 IEC 60870-5-101 point-to-
point
X2
3)
X2
3)
X2, X6
3)
DIAST0 Dial-up traffic Slave X2 X2 X2, X6
ET83 IEC 61850 Ed. 1 (Client,
Server, GOOSE)
1)
X1, X4 X1, X4 X1, X4
ET84 IEC 60870-5-104
2)
X1, X4 X1, X4 X1, X4 X7
ET85 IEC 61850 Ed. 2 (Client,
Server, GOOSE), Ed. 1
(Client)
X1, X4 X1, X4 X1, X4
UMPMT0 IEC 60870-5-101 Master X2 X3 X2 X3 X2, X6 X3, X6
UMPST0 IEC 60870-5-101 Slave X2 X3 X2 X3 X2, X6 X3, X6
Equipable third-party protocols
AGPMT0 AGP interfacing Master X2 X3 X2 X3 X2, X6 X3, X6
BMCUT0 Benning MCU ASCII
protocol
X2
3)
X2
3)
X2, X6
3)
, X6
COUMT0 IEC 62056-21 (IEC 1107)
Master
X2 X3 X2 X3 X2, X6 X3, X6
DNPST0 DNP3 Slave X2 X3 X2 X3 X2, X6 X3, X6
DNPMT0 DNP3 Master X2 X3 X2 X3 X2, X6 X3, X6
DNPiT1 DNP3 TCP/IP Slave X1, X4 X1, X4 X1, X4
DNPiT2 DNP3 TCP/IP Master X1, X4 X1, X4 X1, X4
MODST0 MODBUS RTU Slave X2 X3 X2 X3 X2, X6 X3, X6
MODMT2 MODBUS RTU Master X2 X3 X2 X3 X2, X6 X3, X6
PCBST0 SAT SK 1703 PCMBA
Slave
X2 X3 X2 X3 X2, X6 X3, X6
RP5UT1 ABB RP570/571 Slave X2 X3 X2 X3 X2, X6 X3, X6
SMST0 ASCII protocol for SMS
alerting
X2 X2 X2, X6
ST1ST0 Siemens SINAUT-ST1
Slave
X2 X3 X2 X3 X2, X6 X3, X6
TG8ST0 L&G Telegyr 800 Slave X2 X3 X2 X3 X2, X6 X3, X6
1)
only if Server Ed. 1 is required, else is ET85 to be used
2)
GPRS communication possible via X1, X4 and external GPRS modem
3)
X3 in RS-422 mode