System Components and Technical Data
96 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Communication
2 Ethernet/LAN interfaces
(X1, X4)
Ethernet acc. to IEEE 802.3 (10Base-T or 100Base-TX)
Galvanically insulated
Transmission rate 10 Mbit/s or 100 Mbit/s
Half duplex or full duplex
Auto-MDI(X)
Time synchronization via NTP server
Line length 0…100 m
Rated impulse voltage 2 kV
1 serial interface (X2)
Unbalanced interchange circuit RS-232, V.24/V.28
Galvanically not insulated
ESD protection
Transmission rate up to 115.2 kbit/s (depending on protocol)
Time synchronization
Line length up to 2.5 m
1 serial interface (X3)
Balanced interchange circuit RS-422/RS-485
Galvanically insulated
ESD protection
Configuration 4-wire/2-wire with/without terminating resistor
(parameter-settable)
Transmission rate up to 115.2 kbit/s (depending on protocol)
Rated impulse voltage 2 kV
1 serial interface (X6)
1)
RS-232 Mode:
Unbalanced interchange circuit RS-232, V.28
Galvanically insulated
ESD protection
Transmission rate up to 115.2 kbit/s (depending on proto-
col)Rated impulse voltage 2 kV
Line length up to 2.5 m
RS-485 Mode:
Balanced interchange circuit RS-422/RS-485
Galvanically insulated
ESD protection
Configuration 4-wire/2-wire with/without terminating resistor
(parameter-settable)
Transmission rate up to 115.2 kbit/s (depending on protocol)
Rated impulse voltage 2 kV
1 radio interface (X7)
1)
GPRS
Quad band EGSM 850/900/1800/1900 MHz
GPRS multislot class 10
2)
Coding scheme CS 1-4
Uplink up to 80 kbit/s (HW rev. BB: 60 kbit/s)
Downlink up to 40 kbit/s (Hw rev. BB: 20 kbit/s)
Maximum transmitted RF power:
2 W (33 dBm) for GSM 850 and GSM 900
1 W (30 dBm) for GSM 1800 and GSM 1900
Permitted antenna gain:
GSM 850 MHz 6 dBi
GSM 900 MHz 6 dBi
GSM 1800 MHz 2.25 dBi
GSM 1900 MHz 2.25 dBi
ESD protection
Licensing RED 2014/53/EU

Table of Contents