Setup
3.12 View 5
FST020 Function manual
110 Function Manual, 09/2017, A5E42949526-AA
This parameter is only available if
is set to Fixed.
Setup → Display → View 4 → Trend Scale Upper Limit
Enable or disable
Description
In this parameter View 5 can be enabled.
Default Enabled
If Enabled is selected, all parameters for View 5 must be configured.
Setup → Display → View 5 → Enable or disable
The display View 5 can be configured.
Setting
Single value; Three values; Totalizer; Dosing; 1 value and bargraph; 1 value and graph;
Six values; Six diagnostic values; Alarm list
If Single Value or Dosing is selected,
must be configured.
If Three Values is selected,
,
and
must be configured.
If Totalizer or 1 Value and Graph is selected,
,
and
must be configured.
If 1 Value and Bargraph is selected,
must be configured.
If Six Values or Six Diagnostic Values is selected,
,
,