Maintenance and diagnostics
4.2 Diagnostic events
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
135
4.2.7.11
Input/output events (1)
Description
If one of the selected events appears this affects the status icon, the related status output
and the alarm on the communication interface.
Setting 214 Channel 2 simulated; 215 Channel 3 simulated; 217 Process values frozen; 218 All
outputs forced
Default
Related
The selected events will be shown in the display when they occur. Furthermore, they will be
indicated on the output if
Output (2)
,
Input/output (3)
and/or
Input/output (4)
is set to Status
output and
Status mode
is set to Alarm item.
Path
Maintenance and diagnostics Diagnostic events Enable alarms Input/output events
(1)
4.2.8
Assign alarm class
4.2.8.1
14 - Path 1: No signal
Description
Warning alarms for Path 1
Setting
Process value warning; Maintenance demanded; Maintenance required
Default
Maintenance required
Path
Maintenance and diagnostics Diagnostic events Assign alarm class 14 - Path 1: No
signal
4.2.8.2
148 - Transm. temp. above alarm limit
Description
This event can be mapped to an alarm class respective NAMUR status signal.
Setting
Process value alarm (PA) resp. Out of specification; Maintenance alarm resp. Failure
Default
Process value alarm (PA) resp. Out of specification
Path
Maintenance and diagnostics Diagnostic events Assign alarm class 148 - Transm.
temp. above alarm limit