Setup
3.3 Totalizers
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
59
3.3.1.5
Decimal places
Description
Sets the decimal places for the process value displayed in the local display.
Setting Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal
places; 5 decimal places; 6 decimal places
Default
2 decimal places
Related
Path
Setup Totalizers Totalizer 1 Decimal places
3.3.1.6
Direction
Description
Totalizer 1 direction.
Setting
Forward and backward; Forward; Backward; Hold
Default
Forward
Related
Path
Setup Totalizers Totalizer 1 Direction
3.3.1.7
Fail-safe behaviour
Description
Behaviour of the totalizer during the occurrence of bad input value.
Setting
RUN; totalization is continued using the bad input value; HOLD; totalization is stopped;
MEMORY; totalization is continued based on the last incoming good value
Default
RUN; totalization is continued using the bad input value
Related
Path
Setup Totalizers Totalizer 1 Fail safe mode
3.3.1.8
Reset
Description
Reset totalizer to zero.
Setting
Cancel; OK
Default
Cancel