Maintenance and diagnostics
4.8 Simulation
FST020 Function manual
168 Function Manual, 09/2017, A5E42949526-AA
Setting
Various process alarms can be selected
Default
None selected
Related
This parameter is only available if
Simulation mode
is set to Simulate alarm (ID number).
Path
Maintenance and diagnostics Simulation Simulation alarms Alarms Process
alarms (4)
4.8.3.2.7 Totalizer alarms
Description
The simulation of single and multiple
Totalizer alarms
can be configured.
Setting
Totalizer 1 above alarm limit; Totalizer 1 above warning limit; Totalizer 1 below warning
limit; Totalizer 1 below alarm limit
Default
None selected
Related
This parameter is only available if
Simulation mode
is set to Simulate alarm (ID number).
Path
Maintenance and diagnostics Simulation Simulation alarms Alarms Totalizer
alarms
4.8.3.2.8 Input/output alarms
Description
The simulation of single and multiple
Input/output alarms
can be configured.
Setting
Various input/output alarms can be selected
Default
None selected
Related
This parameter is only available if
Simulation mode
is set to Simulate alarm (ID number).
Path
Maintenance and diagnostics Simulation Simulation alarms Alarms Input/output
alarms
4.8.3.3
Alarm class
Description
The Siemens standard alarm class to be simulated can be configured. The alarm status is
activated on all outputs.