Setup
3.4 Inputs and outputs
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
73
Related
Path
Setup Inputs and outputs Channel 2 - output Current output Lower range value
3.4.3.4.6 Damping value
Description
Sets the Damping (filtering) to smooth out response to sudden changes in measurement.
An increase to Damping value increases response time of device, and affects digital value
and loop current. If output values are noisy, increase Damping value. For faster response
time, decrease Damping value. Find a value that meets requirements of signal stability and
response time.
Setting 0.00 s to 100.00 s
Default
0.00 s
Related
Path
Setup Inputs and outputs Channel 2 - output Current output Damping value
3.4.3.4.7 Fail-safe behaviour
Description
Current output reaction in case of a fault.
Setting
Lower fault current; Upper fault current; Last valid value; Current value; Fail-safe value
Default
Lower fault current
Related
Path Setup Inputs and outputs Channel 2 - output Current output Fail-safe behaviour
3.4.3.4.8 Fail-safe value
Description
Output value in case of a fault and when fail-safe behaviour configured to fail-safe value.
Setting
0.0 mA to 25.0 mA
Default
0.0 mA
Related
Path
Setup Inputs and outputs Channel 2 - output Current output Fail-safe value