Commissioning
6.5 Commissioning optional additional modules
SINAMICS DCP
152 Operating Instructions, 09/2019, A5E34382853K
Removing online in the SINAMICS DCP
Removing a CBE20 without STARTER always leads to the loss of the parameter
assignments which are replaced by the factory settings.
p0009 = 30
p0976 = 1
(recent commissioning)
Removing offline with STARTER
In STARTER, the Control Unit configuration wizard can also be used to subsequently add or
remove a CBE20 (see Section Adding offline in STARTER).
After deleting in the wizard, the project needs to be saved, loaded into the SINAMICS DCP
and permanently saved with RAM → ROM.