Operation
7.1 Operation
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
167
Internal coding of the binector/connector output parameters
Internal coding is required for writing BICO input parameters via PROFIBUS, for example.
Figure 7-5 Internal coding of the binector/connector output parameters
Example: Interconnecting digital signals
A drive is to be traversed via terminals DI 0 and DI 3 on the CUD with ON/OFF1 and "Enable
operation".
Figure 7-6 Interconnecting digital signals (example)
Binector-connector converters and connector-binector converters
Binector-connector converters
Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
word.
p2080[0...15] BI: PROFIdrive PZD send bit-by-bit
Connector-binector converters
A 32-bit integer double word or a 16-bit integer word is converted to individual digital
signals.
p2099[0...1] CI: PROFIdrive PZD selection receive bit-by-bit