Operation
7.4 Communication according to PROFIdrive
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
201
Error values in parameter responses
Table 7- 22 Error values in parameter responses
Error
value
Meaning
Remark
Additional
info
00 hex
Illegal parameter number.
Access to a parameter that does not exist.
–
01 hex Parameter value cannot be changed. Modification access to a parameter value that cannot be
changed.
Subindex
02 hex
Lower or upper value limit exceeded.
Modification access with value outside value limits.
Subindex
03 hex Invalid subindex. Access to a subindex that does not exist. Subindex
04 hex
No array.
Access with subindex to an unindexed parameter.
–
05 hex Wrong data type. Modification access with a value that does not match the
data type of the parameter.
–
06 hex Illegal set operation (only reset al-
lowed).
Modification access with a value not equal to 0 in a case
where this is not allowed.
Subindex
07 hex Description element cannot be
changed.
Modification access to a description element that cannot be
changed.
Subindex
09 hex No description data available. Access to a description that does not exist (the parameter
value exists).
–
10 hex Read job will not be executed. The read request is refused because know-how protection is
active.
0B hex
No operating priority.
Modification access with no operating priority.
–
0F hex No text array exists. Access to a text array that does not exist (the parameter
value exists).
–
11 hex Request cannot be executed due to
operating status.
Access is temporarily not possible for unspecified reasons. –
14 hex Illegal value. Modification access with a value that is within the limits but
is illegal for other permanent reasons (parameter with de-
fined individual values).
Subindex
15 hex Response too long. The length of the present response exceeds the maximum
transfer length.
–
16 hex Illegal parameter address. Illegal or unsupported value for attribute, number of ele-
ments, parameter number, subindex or a combination of
these.
–
17 hex
Illegal format.
Write request: Illegal or unsupported parameter data format.
–
18 hex Number of values inconsistent. Write request: A mismatch exists between the number of
values in the parameter data and the number of elements in
the parameter address.
–
19 hex Drive object does not exist. You have attempted to access a drive object that does not
exist.
–
20 hex
Parameter text cannot be changed
–
–
21 hex
Service not supported.
Illegal or unknown request ID
–
65 hex Parameter presently deactivated. You have tried to access a parameter that, although availa-
ble, does not currently perform a function (e.g. n control set
and access to a V/f control parameter).
–