Operation
7.4 Communication according to PROFIdrive
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
209
Information about the parameter request:
● Request reference:
The value is selected at random from the valid value range. The request reference
establishes the relationship between request and response.
● Request ID:
02 hex → This identifier is required for a write request.
● Drive object No.:
02 hex → The parameters are written to drive 2.
● Number of parameters
04 hex → The multi-parameter request comprises four individual parameter requests.
1st parameter address ... 4th parameter address
● Attribute:
10 hex → The parameter values are to be written.
● Number of elements
01 hex → One array element is written.
● Parameter number
Specifies the number of the parameter to be written to (p0840, p0852, p55050, p50401).
● Subindex:
0 dec → ID of the first array element.
1st parameter value ... 4th parameter value
● Format:
07 hex → Data type, unsigned32
08 hex → Data type, floating point
● Number of values:
01 hex → A value is written to each parameter in the specified format.
● Value:
BICO input parameter: Enter signal source
Adjustable parameter: Enter value