Operation
7.16 Diagnostics
SINAMICS DCP
364 Operating Instructions, 09/2019, A5E34382853K
2 Hz flash-
ing light
DRIVE-CLiQ component firmware update com-
plete. Wait for POWER ON for the respective
Carry out POWER ON for
the respective components
Green/
orange or
red/
orange
1 Hz flash-
ing light
Component detection via LED is activated
(p0124[0]).
Both options depend on the LED state when
component detection is activated via
-
DP1
PROFIdrive
cyclic opera-
tion
- Off Cyclic communication has not (yet) taken place.
The PROFIdrive is ready to communicate when
the CUD is ready for operation (see LED RDY).
-
Green Continuous
Cyclic communication is taking place. -
0.5 Hz
flashing
light
Bus fault (dataEx, no operate)
Full cyclic communication is not yet taking place.
Possible cause:
The controller is not transferring any setpoints.
-
Red Continuous
0.5 Hz
flashing
light
Bus fault (no dataEx)(config fault) -
2 Hz flash-
ing light
Bus fault (no more dataEx)
Bus fault (search baud rate)
OPT
(OPTION)
- Off Electronic power supply is missing or outside
permissible tolerance range,
component not ready for operation,
Option Board not installed,
no associated drive object has been created.
Check power supply and/or
component
Green Continuous
Option Board is ready for operation. -
0.5 Hz
flashing
Depends on the Option Board used -
Red 2 Hz flash-
ing light
At least one fault is present in this component.
Option Board not ready (e.g. after switching on).
Correct the fault and
acknowledge
RDY and DP1 Red 2 Hz flash-
Bus fault – communication has been interrupted. Correct the fault
RDY and OPT Orange 0.5 Hz
flashing
Firmware update in progress for connected Op-
tion Board CBE20.
-