Electrical connection
5.5 Terminals on the CUD and connector board
SINAMICS DCP
60 Operating Instructions, 09/2019, A5E34382853K
Connections for temperature sensors
Connect the sensor according to p50490 (see SINAMICS DCP List
Manual). The cable to the temperature sensor must be shielded and
connected to ground at both ends. The cables from the Temp 1 and
Temp 3 connections to the temperature sensor must have approxi-
mately the same length.
The sense cable (Temp 2) is used to compensate for the cable re-
sistances. If you are not using a sense cable, connect terminals 54
and 55.
Connection with / without sense cable:
55 Temp 3
Memory card slot
Figure 5-13 "Control Unit (CUD)" module, memory card slot
Note
Using the memory card
Using the memory card, see Chapter "
Memory card functions (Page 158)".