EasyManua.ls Logo

Siemens sinamics dcp - Page 75

Siemens sinamics dcp
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
73
Terminal
X177_1, X177_2
Function
Description
57, 58, 59, 60 24 V DC 24 V supply (output) 24 VDC, short-circuit proof
Max. load 200 mA (terminals 9, 10, 57, 58, 59 and
60 combined),
internal supply to digital ground and analog ground
61, 62, 63, 64 M Ground, digital -
"Terminal Module Cabinet (TMC)" module
Table 5- 10 Assignment of the terminals on the Cabinet Board (overview)
Terminal
X177_5
Function
Description
33, 34
M
Ground, analog
-
35, 36
M
Ground, digital
See X177.35 and 36
37, 38
Reserved, do not use
See X177.37 and 38
39, 40
Reserved, do not use
See X177.39 and 40
"Cabinet Board" module
Note:
The terminals on X177_5 are connected in parallel to the terminals with the same name on the Terminal Module Cabinet
(TMC).
Open-loop and closed-loop control section
Table 5- 11 Terminal type, open-loop and closed-loop control section
X177, X177_5 (for option G63):
Type
SPT 1.5 spring-loaded terminal
Connection capacity Rigid/flexible/conductor sizes (mm
2
/mm
2
/AWG): 0.2-1.5 / 0.2-1.5 / 24-16
flexible with conductor end sleeve with/without plastic sleeve:
0.25-1.5 / 0.25-0.75 mm
2
(stripped length 8 mm)
Stripped length
10 mm
X177_1, X177_2 (for option G63):
Type
Two-tier terminal with spring-loaded terminal PK 68
Connection capacity
Rigid/flexible 0.5-2.5 mm
2