Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
73
57, 58, 59, 60 24 V DC 24 V supply (output) 24 VDC, short-circuit proof
Max. load 200 mA (terminals 9, 10, 57, 58, 59 and
60 combined),
internal supply to digital ground and analog ground
61, 62, 63, 64 M Ground, digital -
"Terminal Module Cabinet (TMC)" module
Table 5- 10 Assignment of the terminals on the Cabinet Board (overview)
The terminals on X177_5 are connected in parallel to the terminals with the same name on the Terminal Module Cabinet
Open-loop and closed-loop control section
Table 5- 11 Terminal type, open-loop and closed-loop control section
X177, X177_5 (for option G63):
SPT 1.5 spring-loaded terminal
Connection capacity Rigid/flexible/conductor sizes (mm
2
/mm
2
/AWG): 0.2-1.5 / 0.2-1.5 / 24-16
flexible with conductor end sleeve with/without plastic sleeve:
2
X177_1, X177_2 (for option G63):
Two-tier terminal with spring-loaded terminal PK 68
Rigid/flexible 0.5-2.5 mm
2