Electrical connection
5.6 Additional system components
SINAMICS DCP
92 Operating Instructions, 09/2019, A5E34382853K
Table 5- 25 Screw terminal X530
Connector
Terminal
Designation
1)
Technical specifications
1
DI 4
Voltage: -3 V to +30 V
Electrical isolation: Yes
Reference potential: M2
Input characteristic acc. to IEC 61131-2, type 1
Input voltage (including ripple)
"1" signal: 15 V to 30 V
"0" signal: -3 to +5 V
Input current
at 24 V DC: typ. 9 mA
for "1" signal: > 0.5 mA
Input delay:
For "0" → "1": typ. 50 µs/max. 100 µs
for "1" → "0": typ. 130 µs, max. 150 µs
2
DI 5
3
DI 6
4 DI 7
5
M2
6 M
1)
DI: Digital input; M: Electronics ground; M1, M2: Ground reference
Note
Ensuring the function of digital inputs
An open input is inte
rpreted as "low".
Terminal M1 or M2 must be connected in order that digital inputs (DI) can function.
This is achieved through one of the following measures:
1.
Provide the ground reference of the digital inputs
2.
A jumper to terminal M
Note
: This removes isolation for these digital inputs.