EasyManuals Logo

Siemens SIPROTEC 7UM62 User Manual

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #283 background imageLoading...
Page #283 background image
Functions
2.42 Monitoring Functions
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
283
Measurement Value Acquisition – Currents
In the current paths there are three input transformers each on side 1 and side 2; the digitized sum of the trans-
former currents of one side must be almost zero for generators with isolated starpoint during earth-fault-free
operation. A current circuit fault is detected if
I
F
= | I
L1
+ I
L2
+ I
L3
| > ΣI THRESHOLD S1 · I
N
+ ΣI FACTOR S1 · I
max
or
I
F
= | I
L1
+ I
L2
+ I
L3
| > ΣI THRESHOLD S2 · I
N
+ ΣI FACTOR S2 · I
max
The component ΣI FACTOR S1 · I
max
or ΣI FACTOR S2 · I
max
takes into account admissible current-propor-
tional transformation errors in the input transducers which may occur especially during high fault currents (see
the following figure). The dropout ratio is about 95 %.
This malfunction is reported as „Fail. Σ I Side1“ or „Fail. Σ I Side2“.
The current sum monitoring is only effective for the side for which the starpoint has been configured (address
242 or 244) as Isolated in the power system data.
Figure 2-131 Current sum monitoring
Measured-value Acquisition - Voltages
Four measuring inputs are available in the voltage path: if three of them are used for phase-earth voltages, and
one input for the displacement voltage (e–n voltage from the broken delta winding or neutral transformer) of the
same system, a fault in the phase-earth voltage sum is detected if
| U
L1
+ U
L2
+ U
L3
+ k
U
· U
E
| > SUM.thres. U + SUM.Fact. U x U
max
where SUM.thres. U and SUM.Fact. U are parameter settings, and U
max
is the highest of the phase-earth
voltages. Factor k
U
considers the transformation ratio differences between the displacement voltage input and
the phase voltage inputs (parameter k
U
= Uph / Udelta address 225). The SUM.Fact. U x U
max
component
considers admissible voltage-proportional transformation errors of the input transducers, which can be espe-
cially large in the presence of high voltages (see the following figure).
This malfunction is reported as „Fail Σ U Ph-E“.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UM62 and is the answer not in the manual?

Siemens SIPROTEC 7UM62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UM62
CategoryProtection Device
LanguageEnglish

Related product manuals