Introduction
1.3 Characteristics
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
33
User-defined Functions
Internal and external signals can be logically combined to establish user-defined logic functions.
All common logic functions (AND, OR, NOT, Exclusive OR, etc.).
Time delays and limit value interrogations.
Processing of measured values, including zero suppression, adding a knee characteristic for a transducer
input, and live-zero monitoring.
Breaker Control
Circuit breakers can be opened and closed manually via programmable function keys, via the system inter-
face (e.g. by SICAM or LSA), or via the operating interface (using a PC with DIGSI).
Feedback information on circuit breakers states via the breaker auxiliary contacts.
Plausibility monitoring of the circuit breaker position and monitoring of interlocking conditions for switching
operations.
Measuring Transducer
If the 3 measuring transducers present in the unit are not needed by the protection functions, they can be
used to connect any type of analog signals (± 10 V, ± 20 mA).
Threshold processing and logical linking of measurement signals possible.
Measurement Monitoring
Increased reliability thanks to monitoring of internal measuring circuits, auxiliary power supply, hardware and
software.
Current transformer and voltage transformer secondary circuits are monitored using symmetry checks.
Trip circuit monitoring possible via external circuitry.
Phase sequence check.