EasyManuals Logo

Siemens SIPROTEC 7UM62 User Manual

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #422 background imageLoading...
Page #422 background image
Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
422
Symmetrical Current Test
The operational measured values supplied by the 7UM62 device allow a fast commissioning without external
instruments. The indices of the measured currents are as follows:
The symbol for current I is followed by the phase identifier Lx and by the index of the side of the protected object
(e.g. the transformer winding). Example:
IL1S1 Current in phase L1 on side 1.
Absolute Value Measurement
Compare the current magnitudes under Measurement Secondary Values Operational values second-
ary with the actually flowing values:
IL1S1 =
IL2S1 =
IL3S1 =
IL1S2 =
IL2S2 =
IL3S2 =
If deviations occur that cannot be explained by measuring tolerances, either a connection or the test setup is
wrong:
Disconnect the protected object (shut down generator), and earth it,
Re-check the plant connections to the device and the test arrangement and correct them.
Repeat measurement and recheck measured values.
Angle Measurement
If the current magnitudes are consistent, the next step is to check the phase angle relations between the cur-
rents (ϕIL1S1, ϕIL2S1, ϕIL3S1, ϕIL1S2, ϕIL2S2, ϕIL3S2). The angle differences are in each case referred to
winding L1 of side 1.
Check the phase angle under Measurement Secondary Values Phase angles of side 1 of the protected
object. All angles are referred to IL1S1.
Consequently, a clockwise phase rotation should produce roughly the following results:
ϕL1S1 = 0°
ϕL2S1 = 240°
ϕL3S1 = 120°
If the angles are not correct, wrong polarity or connection phase interchange at side 1 is the cause.
Disconnect the protected object (shut down generator), and earth it,
Re-check the plant connections to the device and the test arrangement and correct them.
Repeat measurement and recheck measured values.
Check the phase angle under Measurement
Secondary Values Phase angles of side 2 of the device.
All angles are referred to IL1S1. If the angles are not correct, wrong polarity or line phase interchange at side
2 is the cause; proceed as for side 1.
The angles of the through-flowing currents between the different sides of the protection object are defined such
that a current of equal phase flowing through the protected object, provided that the connections are correct,
produces the angle difference at the two measuring points of 180° between currents of the same phase. Ex-
ception:Transverse differential protection where both currents must be in phase!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UM62 and is the answer not in the manual?

Siemens SIPROTEC 7UM62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UM62
CategoryProtection Device
LanguageEnglish

Related product manuals