EasyManuals Logo

Siemens SIPROTEC 7UM62 User Manual

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #444 background imageLoading...
Page #444 background image
Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
444
Caution!
Under-excitation may cause the generator to fall out of step!
Nonobservance of the following procedures can result in minor injury or material damage.
Operation with underexcitation is admissible only for a short period
Proceed as follows:
1. Adjust excitation until the reactive power amounts to approximately Q = 0. To check this, read out the active
power P
0
and the reactive power Q
0
with their respective signs and note them down (see table below).
2. Slowly increase excitation to 30% of rated apparent power of generator (overexcited).
Read out the motoring power with polarity (negative sign) in the operational measured values and note
it down as P
1
(see table below).
Read out the reactive power Q
1
with polarity (positive sign) and write it down.
3. Reduce excitation slowly to approximately 30% rated apparent power of generator (underexcited).
Read out the motoring power P
2
with polarity (negative sign) in the operational measured values under
and write it down (see table below).
Read out the reactive power Q
2
with polarity (negative sign) in the operational measured values and
write it down (see table below).
4. Adjust generator to no-load excitation and shut it down or select the desired operational state.
Figure 3-39 Determination of the correction angle W0
The read-out measured values P
1
, and P
2
are now used to carry out CT angle error correction. First calculate
a correction angle from the measured value pairs according to the following formula:
The power values must be inserted with their correct polarity as read out! Otherwise faulty result!
This angle ϕ
corr
is entered with identical sign as the new correction angle under address 204 CT ANGLE W0:
Setting value CT ANGLE W0 = ϕ
corr
A quarter of the sum of the measured values P
1
+ P
2
, also with negative signs, is set as pickup value of the
reverse power protection P> REVERSE under address 3102.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UM62 and is the answer not in the manual?

Siemens SIPROTEC 7UM62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UM62
CategoryProtection Device
LanguageEnglish

Related product manuals