Technical Data
4.1 General
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
456
Binary Outputs
LEDs
Signalling/trip relays
1)
(see also terminal assignments in Appendix A.2))
Number: According to the order variant (allocatable)
7UM621*- 12 (1 NO contact each, 3 optionally as NC contacts)
7UM623*-
7UM622*- 20 (1 NO contact each, 4 optionally as NC contacts)
1 Life contact (NC contact or NO contact, selectable)
Make/break capacity CLOSE 1000 W/VA
BREAK 30 VA
40 W resistive
25 W/VA at L/R ≤ 50 ms
Switching voltage 250 V
Permissible current per contact
(continuous)
5A
Permissible current per contact
(close and hold)
30 A for 0.5 S (NO contact)
Permissible total current on common
path
5 A continuous
30 A for 0.5 s
1
) UL-listed with the following rated data:
AC 120 V Pilot duty, B300
AC 240 V Pilot duty, B300
AC 240 V 5 A General Purpose
DC 24 V 5 A General Purpose
DC 48 V 0.8 A General Purpose
DC 240 V 0.1 A General Purpose
AC 120 V 1/6 hp (4.4 FLA)
AC 240 V 1/2 hp (4.9 FLA)
Number
RUN (green) 1
ERROR (red) 1
allocatable LEDs (red) 14