EasyManua.ls Logo

Siemens SIPROTEC 7UM62 - Page 579

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.7 Settings
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
579
2031 I-DIFF>> Diff. Prot 0.5 .. 12.0 I/InO; 7.5 I/InO Pickup Value of High Set Trip
2036A T I-DIFF>> Diff. Prot 0.00 .. 60.00 sec; 0.00 sec T I-DIFF>> Time Delay
2041A SLOPE 1 Diff. Prot 0.10 .. 0.50 0.25 Slope 1 of Tripping Characteristic
2042A BASE POINT 1 Diff. Prot 0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope 1 of Charac.
2043A SLOPE 2 Diff. Prot 0.25 .. 0.95 0.50 Slope 2 of Tripping Characteristic
2044A BASE POINT 2 Diff. Prot 0.00 .. 10.00 I/InO 2.50 I/InO Base Point for Slope 2 of Charac.
2051A I-REST. STARTUP Diff. Prot 0.00 .. 2.00 I/InO 0.10 I/InO I-RESTRAINT for Start Detection
2052A START-FACTOR Diff. Prot 1.0 .. 2.0 1.0 Factor for Increasing of Char. at
Start
2053 T START MAX Diff. Prot 0.0 .. 180.0 sec 5.0 sec Maximum Permissible Starting
Time
2061A I-ADD ON STAB. Diff. Prot 2.00 .. 15.00 I/InO 4.00 I/InO Pickup for Add-on Stabilization
2062A T ADD ON-STAB. Diff. Prot 2 .. 250 Cycle; 15 Cycle Duration of Add-on Stabilization
2063A CROSSB. ADD ON Diff. Prot 2 .. 1000 Cycle; 0; 15 Cycle Time for Cross-blocking Add-on
Stabiliz.
2071 2. HARMONIC Diff. Prot 10 .. 80 % 15 % 2nd Harmonic Content in I-DIFF
2072A CROSSB. 2. HARM Diff. Prot 2 .. 1000 Cycle; 0; 3 Cycle Time for Cross-blocking 2nd
Harm.
2076 n. HARMONIC Diff. Prot 10 .. 80 % 30 % n-th Harmonic Content in I-DIFF
2077A CROSSB. n.HARM Diff. Prot 2 .. 1000 Cycle; 0; 0 Cycle Time for Cross-blocking n-th
Harm.
2078A IDIFFmax n.HM Diff. Prot 0.5 .. 12.0 I/InO 1.5 I/InO Limit IDIFFmax of n-th Harm.Re-
straint
2101 REF PROT. REF OFF
ON
Block relay
OFF Restricted Earth Fault Protection
2102 REF I> BLOCK REF 1.0 .. 2.5 I/InO 1.5 I/InO REF Pickup of Phase Current
Blocking
2103 REF U0>RELEASE REF 1.0 .. 100.0 V; 0 5.0 V REF Pickup of U0> Release
2110 I-REF> REF 0.05 .. 2.00 I/InO 0.10 I/InO I-REF> Pickup
2112 T I-REF> REF 0.00 .. 60.00 sec; 0.00 sec T I-REF> Time Delay
2113A SLOPE REF 0.00 .. 0.95 0.25 Slope of Charac. I-REF> = f(I0-
Rest)
2114A BASE POINT REF 0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope of Charac-
teristic
3001 UNDEREXCIT. Underexcitation OFF
ON
Block relay
OFF Underexcitation Protection
3002 1/xd CHAR. 1 Underexcitation 0.20 .. 3.00 0.41 Susceptance Intersect Charac-
teristic 1
3003 ANGLE 1 Underexcitation 50 .. 120 ° 80 ° Inclination Angle of Characteris-
tic 1
3004 T CHAR. 1 Underexcitation 0.00 .. 60.00 sec; 10.00 sec Characteristic 1 Time Delay
3005 1/xd CHAR. 2 Underexcitation 0.20 .. 3.00 0.36 Susceptance Intersect Charac-
teristic 2
3006 ANGLE 2 Underexcitation 50 .. 120 ° 90 ° Inclination Angle of Characteris-
tic 2
3007 T CHAR. 2 Underexcitation 0.00 .. 60.00 sec; 10.00 sec Characteristic 2 Time Delay
3008 1/xd CHAR. 3 Underexcitation 0.20 .. 3.00 1.10 Susceptance Intersect Charac-
teristic 3
3009 ANGLE 3 Underexcitation 50 .. 120 ° 90 ° Inclination Angle of Characteris-
tic 3
3010 T CHAR 3 Underexcitation 0.00 .. 60.00 sec; 0.30 sec Characteristic 3 Time Delay
3011 T SHRT Uex< Underexcitation 0.00 .. 60.00 sec; 0.50 sec T-Short Time Delay (Char. &
Uexc<)
3012 EXCIT. VOLT. Underexcitation ON
OFF
OFF State of Excitation Volt. Supervi-
sion
3013 Uexcit. < Underexcitation 0.50 .. 8.00 V 2.00 V Excitation Voltage Superv.
Pickup
3014A Umin Underexcitation 10.0 .. 125.0 V 25.0 V Undervoltage blocking Pickup
Addr. Parameter Function C Setting Options Default Setting Comments