Appendix
A.8 Information List
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
602
5091 Reverse power prot. is switched
OFF (Pr OFF)
Reverse Power OUT on
off
**LEDBO70811Yes
5092 Reverse power protection is
BLOCKED (Pr BLOCKED)
Reverse Power OUT on
off
on off * LED BO 70 82 1 Yes
5093 Reverse power protection is
ACTIVE (Pr ACTIVE)
Reverse Power OUT on
off
**LEDBO70831Yes
5096 Reverse power: picked up (Pr
picked up)
Reverse Power OUT * on off * LED BO 70 84 2 Yes
5097 Reverse power: TRIP (Pr TRIP) Reverse Power OUT * on m LED BO 70 85 2 Yes
5098 Reverse power: TRIP with stop
valve (Pr+SV TRIP)
Reverse Power OUT * on m LED BO 70 86 2 Yes
5113 >BLOCK forward power supervi-
sion (>Pf BLOCK)
Forward Power SP * * * LED BI BO
5116 >BLOCK forw. power superv. Pf<
stage (>Pf< BLOCK)
Forward Power SP on
off
* * LED BI BO 70 102 1 Yes
5117 >BLOCK forw. power superv. Pf>
stage (>Pf> BLOCK)
Forward Power SP on
off
* * LED BI BO 70 103 1 Yes
5121 Forward power supervis. is
switched OFF (Pf OFF)
Forward Power OUT on
off
* * LED BO 70 106 1 Yes
5122 Forward power supervision is
BLOCKED (Pf BLOCKED)
Forward Power OUT on
off
on off * LED BO 70 107 1 Yes
5123 Forward power supervision is
ACTIVE (Pf ACTIVE)
Forward Power OUT on
off
* * LED BO 70 108 1 Yes
5126 Forward power: Pf< stage picked
up (Pf< picked up)
Forward Power OUT * on off * LED BO 70 109 2 Yes
5127 Forward power: Pf> stage picked
up (Pf> picked up)
Forward Power OUT * on off * LED BO 70 110 2 Yes
5128 Forward power: Pf< stage TRIP
(Pf< TRIP)
Forward Power OUT * on m LED BO 70 111 2 Yes
5129 Forward power: Pf> stage TRIP
(Pf> TRIP)
Forward Power OUT * on m LED BO 70 112 2 Yes
5143 >BLOCK I2 (Unbalance Load)
(>BLOCK I2)
Unbalance Load SP * * * LED BI BO
5145 >Reverse Phase Rotation (>Re-
verse Rot.)
P.System Data 1 SP on
off
**LEDBIBO71341Yes
5146 >Reset memory for thermal
replica I2 (>RM th.rep. I2)
Unbalance Load SP on
off
**LEDBIBO
5147 Phase Rotation L1L2L3 (Rotation
L1L2L3)
P.System Data 1 OUT on
off
* * LED BO 70 128 1 Yes
5148 Phase Rotation L1L3L2 (Rotation
L1L3L2)
P.System Data 1 OUT on
off
* * LED BO 70 129 1 Yes
5151 I2 is switched OFF (I2 OFF) Unbalance Load OUT on
off
* * LED BO 70 131 1 Yes
5152 I2 is BLOCKED (I2 BLOCKED) Unbalance Load OUT on
off
on off * LED BO 70 132 1 Yes
5153 I2 is ACTIVE (I2 ACTIVE) Unbalance Load OUT on
off
* * LED BO 70 133 1 Yes
5156 Unbalanced load: Current
warning stage (I2> Warn)
Unbalance Load OUT on
off
* * LED BO 70 134 1 Yes
5158 Reset memory of thermal replica
I2 (RM th.rep. I2)
Unbalance Load OUT on
off
* * LED BO 70 137 1 Yes
5159 I2>> picked up (I2>> picked up) Unbalance Load OUT * on off * LED BO 70 138 2 Yes
5160 Unbalanced load: TRIP of current
stage (I2>> TRIP)
Unbalance Load OUT * on m LED BO 70 139 2 Yes
5161 Unbalanced load: TRIP of
thermal stage (I2 Θ TRIP)
Unbalance Load OUT * on * LED BO 70 140 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation