Appendix
A.8 Information List
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
605
5369 Reset memory of thermal replica
U/f (RM th.rep. U/f)
Overexcitation OUT on
off
**LEDBO71881Yes
5370 Overexc. prot.: U/f> picked up
(U/f> picked up)
Overexcitation OUT * on off * LED BO 71 89 2 Yes
5371 Overexc. prot.: TRIP of U/f>>
stage (U/f>> TRIP)
Overexcitation OUT * on m LED BO 71 90 2 Yes
5372 Overexc. prot.: TRIP of th. stage
(U/f> th.TRIP)
Overexcitation OUT * on * LED BO 71 91 2 Yes
5373 Overexc. prot.: U/f>> picked up
(U/f>> pick.up)
Overexcitation OUT * on off * LED BO 71 92 2 Yes
5381 >BLOCK rotor earth fault prot. (1-
3Hz) (>REF 1-3Hz BLK)
REF 1-3Hz SP * * * LED BI BO
5383 >BLOCK rotor earth fault prot.
(R,fn) (>BLOCK R/E/F)
Rotor E/F SP * * * LED BI BO
5386 >Test rotor earth fault prot. (1-
3Hz) (>Test REF 1-3Hz)
REF 1-3Hz SP on
off
* * LED BI BO 71 116 1 Yes
5387 REF protection (1-3Hz) is
switched OFF (REF 1-3Hz OFF)
REF 1-3Hz OUT on
off
* * LED BO 71 117 1 Yes
5388 REF protection (1-3Hz) is
BLOCKED (REF 1-3Hz BLK)
REF 1-3Hz OUT on
off
on off * LED BO 71 118 1 Yes
5389 REF protection (1-3Hz) is
ACTIVE (REF 1-3Hz ACT)
REF 1-3Hz OUT on
off
* * LED BO 71 119 1 Yes
5391 Rotor earth fault prot. (R,fn) swit.
OFF (R/E/F OFF)
Rotor E/F OUT on
off
* * LED BO 71 121 1 Yes
5392 Rotor earth fault prot. (R,fn)
BLOCKED (R/E/F BLOCKED)
Rotor E/F OUT on
off
on off * LED BO 71 122 1 Yes
5393 Rotor earth fault prot. (R,fn) is
ACTIVE (R/E/F AKTIVE)
Rotor E/F OUT on
off
* * LED BO 71 123 1 Yes
5394 Rot. earth flt. prot. (R,fn) block by
U< (R/E/F U< block)
Rotor E/F OUT on
off
* * LED BO 71 124 1 Yes
5395 REF protection (1-3Hz) open
circuit (REF 1-3Hz open)
REF 1-3Hz OUT on
off
* * LED BO 71 125 1 Yes
5396 Failure R/E/F protection IEE<
(Fail. REF IEE<)
Sens. E Fault OUT on
off
* * LED BO 71 126 1 Yes
5397 Rot. earth flt.prot. (R,fn) Re<
warning (R/E/F warning)
Rotor E/F OUT on
off
* * LED BO 71 127 1 Yes
5398 Rot. earth flt.prot. (R,fn) Re<<
pick.up (R/E/F picked up)
Rotor E/F OUT * on off * LED BO 71 128 2 Yes
5399 Rotor earth fault prot. (R,fn) Re<<
TRIP (R/E/F TRIP)
Rotor E/F OUT * on m LED BO 71 129 2 Yes
5400 Failure rotor earth fault prot.
(R,fn) (Failure R/E/F)
Rotor E/F OUT on
off
* * LED BO 71 130 1 Yes
5401 Failure REF protection (1-3Hz)
(Fail REF 1-3Hz)
REF 1-3Hz OUT on
off
* * LED BO 71 131 1 Yes
5403 REF prot. (1-3Hz) warning stage
(Re<) (REF 1-3Hz Warn)
REF 1-3Hz OUT on
off
* * LED BO 71 133 1 Yes
5406 REF prot. (1-3Hz) Re<< picked
up (REF 1-3Hz Fault)
REF 1-3Hz OUT * on off * LED BO 71 136 2 Yes
5407 REF prot. (1-3Hz) Re<< TRIP
(REF 1-3Hz Trip)
REF 1-3Hz OUT * on * LED BO 71 137 2 Yes
5408 REF prot. (1-3Hz) test passed
(Test REF PASSED)
REF 1-3Hz OUT on
off
* * LED BO 71 138 1 Yes
5409 REF prot. (1-3Hz) test NOT
passed (Test REF Fail.)
REF 1-3Hz OUT on
off
* * LED BO 71 139 1 Yes
5410 REF (1-3Hz) 1 Measuring circuit
open (1 Cir. open)
REF 1-3Hz OUT on
off
**LEDBO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation