Appendix
A.8 Information List
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
607
5519 Stage df4/dt picked up (df4/dt
pickup)
df/dt Protect. OUT * on off * LED BO 72 12 2 Yes
5520 Stage df1/dt TRIP (df1/dt TRIP) df/dt Protect. OUT * on * LED BO 72 13 2 Yes
5521 Stage df2/dt TRIP (df2/dt TRIP) df/dt Protect. OUT * on * LED BO 72 14 2 Yes
5522 Stage df3/dt TRIP (df3/dt TRIP) df/dt Protect. OUT * on * LED BO 72 15 2 Yes
5523 Stage df4/dt TRIP (df4/dt TRIP) df/dt Protect. OUT * on * LED BO 72 16 2 Yes
5533 >BLOCK inadvertent energ. prot.
(>BLOCK I.En.)
Inadvert. En. SP * * * LED BI BO
5541 Inadvert. Energ. prot. is swiched
OFF (I.En. OFF)
Inadvert. En. OUT on
off
**LEDBO72311Yes
5542 Inadvert. Energ. prot. is
BLOCKED (I.En. BLOCKED)
Inadvert. En. OUT on
off
on off * LED BO 72 32 1 Yes
5543 Inadvert. Energ. prot. is ACTIVE
(I.En. ACTIVE)
Inadvert. En. OUT on
off
**LEDBO72331Yes
5546 Release of the current stage
(I.En. release)
Inadvert. En. OUT on
off
**LEDBO72341Yes
5547 Inadvert. Energ. prot. picked up
(I.En. picked up)
Inadvert. En. OUT * on off * LED BO 72 35 2 Yes
5548 Inadvert. Energ. prot. TRIP (I.En.
TRIP)
Inadvert. En. OUT * on m LED BO 72 36 2 Yes
5553 >BLOCK SEF with 3.Harmonic
(>SEF 3H BLOCK)
SEF 3.Harm. SP * * * LED BI BO
5561 SEF with 3.Harm. is switched
OFF (SEF 3H OFF)
SEF 3.Harm. OUT on
off
**LEDBO72511Yes
5562 SEF with 3.Harm. is BLOCKED
(SEF 3H BLOCK)
SEF 3.Harm. OUT on
off
on off * LED BO 72 52 1 Yes
5563 SEF with 3.Harm. is ACTIVE
(SEF 3H ACTIVE)
SEF 3.Harm. OUT on
off
**LEDBO72531Yes
5567 SEF with 3.Harm. picked up (SEF
3H pick.up)
SEF 3.Harm. OUT * on off * LED BO 72 54 2 Yes
5568 SEF with 3.Harm. TRIP (SEF 3H
TRIP)
SEF 3.Harm. OUT * on m LED BO 72 55 2 Yes
5571 >BLOCK startup O/C protection
(>BLOCK O/C St)
O/C Startup SP * * * LED BI BO
5572 Startup O/C protection is
switched OFF (O/C Start OFF)
O/C Startup OUT on
off
**LEDBO72621Yes
5573 Startup O/C protection is
BLOCKED (O/C Start BLK)
O/C Startup OUT on
off
on off * LED BO 72 63 1 Yes
5574 Startup O/C protection is ACTIVE
(O/C Start ACT)
O/C Startup OUT on
off
**LEDBO72641Yes
5575 Startup O/C phase L1 picked up
(O/C Start L1 PU)
O/C Startup OUT * on off * LED BO 72 65 2 Yes
5576 Startup O/C phase L2 picked up
(O/C Start L2 PU)
O/C Startup OUT * on off * LED BO 72 66 2 Yes
5577 Startup O/C phase L3 picked up
(O/C Start L3 PU)
O/C Startup OUT * on off * LED BO 72 67 2 Yes
5578 Startup O/C protection TRIP (O/C
Start TRIP)
O/C Startup OUT * on * LED BO 72 68 2 Yes
5581 >BLOCK Vector Jump (>VEC
JUMP block)
Vector Jump SP * * * LED BI BO
5582 Vector Jump is switched OFF
(VEC JUMP OFF)
Vector Jump OUT on
off
**LEDBO72721Yes
5583 Vector Jump is BLOCKED (VEC
JMP BLOCKED)
Vector Jump OUT on
off
on off * LED BO 72 73 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation