132
Configuration Menu
16.6.2 Text message (SMS) notifications
Procedure
•
Activate the Text message (SMS) notification button.
•
The Sending time can be entered in the text field.
It is recommended to select a sending time when the inverters are no longer feeding power.
•
Check the days on which the e-mails should be sent. E-mails are only sent on the days checked.
•
SAVE the settings.
16.7 Alarm (only Solar-Log 1000 and 2000)
The Solar-Log™ continuously monitors its internal alarm contact. If this contact is opened, it sets off an
alarm which can be indicated in various ways. In the
Alarm tab, the alarm contact can be activated and
different types of notification can be configured.
Activating alarm contact
Procedure:
•
Select Configuration | Plant | Plant groups from the menu.
•
Activate the Activate Alarm Contact button.
•
SAVE the settings.
After activating alarm notifications, a triggered alarm can be indicated by:
•
E-mail
•
Text message (SMS)
•
Relay
•
Speaker
.The e-mail and text message (SMS) settings must be pre-configured.
Procedure
•
Activate the desired Notifications.
•
SAVE the settings.
Test section
Here you have the option to perform an alarm test.
16.8 Power & Failure
Performance monitoring is based on a comparison of the power out from all of the inverters, including
individual trackers in the case of inverters with more than one tracker or, as the case may be, sensors. If
the target power deviates from the actual power by more than a certain tolerance (= min. feed-in power),
a notification can be sent by e-mail and/or text message (SMS) after the selected fault duration has been
reached.
If an individual module loses power, the string power for the same level of irradiation will drop, and can
thus be detected and reported.
Power comparison always works reliably, even if the weather is cloudy. The important thing is that all
modules should not be overshadowed. Therefore, the monitoring period should be scheduled for periods
when there are no shadows.
As power measurement in the inverter is very inaccurate under a certain threshold, a minimum percentage
value can also be specified below which monitoring is interrupted.
Procedure