Configuration Menu
Note!
The notifications per e-mail for active power reductions can be activated from the Confi-
guration | Notifications | PM
menu.
16.12.3 Remote controlled active power reduction with the calculation of
self-consumption (only Solar-Log™ PM+)
This function is an enhancement to the Remote controlled active power reduction function described in
the previous chapter. This function does not correspond to provisions of the German EEG laws and has to
be arranged with the grid operator before being used.
Note!
The Solar-Log PM+ needs to be
linked to a consumption meter to implement this function. Please note the instructions in
chapter “12.5 External power meter“.
The configuration of this corresponds to that already described for the remote controlled active power
reduction.
The instruction for integrating the meters into the electric wiring of the house or building are found in the
appendix.
Notes about
the function!
Self-consumption is taken into account with a command (less than 100% and greater
than 0%). The inverter(s) supply a higher output than the command value by taking the
current consumption into account.
Self-consumption is not taken into account with the 0% command value. As a safeguard
here, the plant is always limited to 0%.
16.12.4 70% fi xed reduction
By activating this menu item the inverter(s) are controlled to be fixed at 70% of the installed DC power.
Enter the
Maximum AC Power and Connected Generator Power as reference values in the Configurati-
on | Devices | Configuration
menu.
The maximum power output for the inverters can be calculated from the connected generator power value
that has been entered.