Motion Coordinator Technical Reference Manual
Expansion Modules 5-9
Input/Output Modules
Software Interfacing
The Motion Coordinator will automatically detect and allow the use of correctly
connected CAN I/O channels. The CAN I/O are accessed with the same
IN
and
OP
commands used to access the built-in I/O on the Motion Coordinator. The
Motion Coordinator sets the system parameter
NIO
which reflects the number of
I/O's connected to the system. 3 system parameters are available to facilitate
the use of the CAN 16-I/O:
CANIO_STATUS, CANIO_ADDRESS and CANIO_ENABLE
When choosing which I/O devices should be connected to which channels the fol-
lowing points need to be considered:
Inputs 0 - 31 ONLY are available for use with system parameters which specify
an input, such as
FWD_IN, REV_IN, DATUM_IN etc.
Outputs 8 - 31 ONLY are available for use with the
PSWITCH command.
The built-in I/O channels have the fastest operation <1mS
CAN I/O channels 16 - 64 have the next fastest operation <2mS
CAN I/O channels 64 - 191 have the next fastest operation <8mS
It is not possible to mix the CAN 16-I/O module which is running the TRIO I/O pro-
tocol with DeviceNet equipment on the same network.
Troubleshooting
If the network configuration is incorrect 2 indications will be seen: The CAN 16-I/
O module will indicate that it is uninitialised and the Motion Coordinator will
report the wrong number when questioned:
>>? NIO
If this is not as expected check:
Terminating 120 Ohm Network Resistors fitted?
24Volt Power to each IO bank required?
24Volt Power to Network?
DIP switches in sequence starting 0,1,2...?
System Software Version 1.40 (or higher)?
Motion Coordinator CANIO_ADDRESS=32?