Pipe Design TITANUS MICRO·SENS
®
4 – 6 Data: 01/09 MS_A_04-en-e
Bends are to be preferred over angles.
An excessive number of changes in direction can change the detection
time.
Special cases If the pipe system does not match the project planning guidelines de-
scribed here due to structural constraints, WAGNER should make the in-
dividual calculations for such a case.
Checking Check detection reliability with activation tests in cases where use of the
system is critical. Also check whether an air flow rate is present at indi-
vidual aspiration apertures.
The fan voltage can be increased in order to reduce transport time.
Make sure that the current intake increases.
INSTRUCTION
TIP