Part 4 PBX power supply 725
[1] Power circuit breaker
[2] Mains cord (length 2m)
Fig. 4.17: Power supply unit socket and power supply area main board 2065
4.1.1 Uninterruptible power supply (UPS)
The use of an uninterruptible power supply (UPS) guarantees that the PBX can be
operated even in the event of a failure of the 230 V power supply.
Uninterruptible power supply can be provided by the UPS-12V module or an
external UPS.
4.1.1.1 UPS with UPS-12V module
The charging circuit of the UPS-12V module is designed for lead-acid batteries
with a floating charge voltage of approx. 13.6 V. The charge current can be lim-
ited to 1 or 2 A (jumper on the module). The battery switching circuit is protected
on the module with 20 A (Wickmann FK1 20 A). If the polarity is the wrong way
around, the fuse breaks the circuit and must then be replaced.
If a battery isolating point is provided, it must be equipped to handle a current of
20 A (at 12 VDC).
[1]
haz1198aadeb0
230 V
[2]