Chapter 4: AC Drive Parameters
Page 4–11
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
GS4 Parameters Summary – Analog Parameters (P4.xx) – (continued)
Parameter Range
Run
Read/
Write
Modbus
Address
Settings
Hex Dec Default User
P4.16
AI2 Input Bias (Offset) Polarity
0: NO Offset
1: Positive Offset
2: Negative Offset
R/W 0410 41041 0
P4.17
AI2 Input Gain -500�0% to +500�0% ♦R/W 0411 41042 100�0
P4.18
AI2 Filter 0�00~20�00 sec ♦R/W 0412 41043 0�01
P4.19
AI3 Input Bias (Offset) -100�0% to +100�0% ♦R/W 0413 41044 0
P4.20
AI3 Input Bias (Offset) Polarity
0: NO Offset
1: Positive Offset
2: Negative Offset
R/W 0414 41045 0
P4.21
+AI3 Input Gain -500�0% to +500�0% ♦R/W 0415 41046 100�0
P4.22
-AI3 Input Gain -500�0% to +500�0% ♦R/W 0416 41047 100�0
P4.23
AI3 Filter 0�00~20�00 sec ♦R/W 0417 41048 0�01
P4.24
AI V/Hz Calculated Selection
0: All Inputs Use Bias and Gain
1: AI1 Custom V/Hz
2: AI2 Custom V/Hz
3: AI1 and AI2 Custom V/Hz
4: AI3 Custom V/Hz
5: AI1 & AI3 Custom V/Hz
6: AI2 & AI3 Custom V/Hz
7: All Custom V/Hz
R/W 0418 41049 0
P4.25
AI1 Low V/A
P4�05=0: 0�00~10�00V
P4�05=1: 4�00~20�00mA
P4�05=2: 0�00~20�00mA
R/W 0419 41050
P4 �05=0:
0�00V
P4 �05=1:
4�00mA
P4 �05=2:
0�00mA
P4.26
AI1 Low Hz Percent 0�00~100�00% R/W 041A 41051 0
P4.27
AI1 Mid V/A
P4�05=0: 0�00~10�00V
P4�05=1: 4�00~20�00mA
P4�05=2: 0�00~20�00mA
R/W 041B 41052
P4 �05=0:
5�00V
P4 �05=1:
12�00mA
P4 �05=2:
10�00mA
P4.28
AI1 Mid Hz Percent 0�00~100�00% R/W 041C 41053 50�00
P4.29
AI1 High V/A
P4�05=0: 0�00~10�00V
P4�05=1: 4�00~20�00mA
P4�05=2: 0�00~20�00mA
R/W 041D 41054
P4 �05=0:
10�00V
P4 �05=1:
20�00mA
P4 �05=2:
20�00mA
P4.30
AI1 High Hz Percent 0�00~100�00% R/W 041E 41055 100�00
P4.31
AI2 Low V/A
P4�06=0: 0�00~10�00V
P4�06=1: 4�00~20�00mA
P4�06=2: 0�00~20�00mA
R/W 041F 41056
P4 �06=0:
0�00V
P4 �06=1:
4�00mA
P4 �06=2:
0�00mA
P4.32
AI2 Low Hz Percent 0�00~100�00% R/W 0420 41057 0
P4.33
AI2 Mid V/A
P4�06=0: 0�00~10�00V
P4�06=1: 4�00~20�00mA
P4�06=2: 0�00~20�00mA
R/W 0421 41058
P4 �06=0:
5�00V
P4 �06=1:
12�00mA
P4 �06=2:
10�00mA
P4.34
AI2 Mid Hz Percent 0�00~100�00% R/W 0422 41059 50�00
(table continued next page)

Table of Contents

Other manuals for Automation Direct DURApulse GS4