Page 4–12
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
GS4 Parameters Summary – Analog Parameters (P4.xx) – (continued)
Parameter Range
Run
Read/
Write
Modbus
Address
Settings
Hex Dec Default User
P4.35
AI2 High V/A
P4�06=0: 0�00~10�00V
P4�06=1: 4�00~20�00mA
P4�06=2: 0�00~20�00mA
R/W 0423 41060
P4 �06=0:
10�00V
P4 �06=1:
20�00mA
P4 �06=2:
20�00mA
P4.36
AI2 High Hz Percent 0�00~100�00% R/W 0424 41061 100�00
P4.37
AI3 Low Voltage Unipolar 0�00~10�00V R/W 0425 41062 0
P4.38
AI3 Low Hz Percent Unipolar 0�00~100�00% R/W 0426 41063 0
P4.39
AI3 Mid Voltage Unipolar 0�00~10�00V R/W 0427 41064 5�00
P4.40
AI3 Mid Hz Percent Unipolar 0�00~100�00% R/W 0428 41065 50�00
P4.41
AI3 High Voltage Unipolar 0�00~10�00V R/W 0429 41066 10�00
P4.42
AI3 High Hz Percent Unipolar 0�00~100�00% R/W 042A 41067 100�00
P4.43
-AI3 High Voltage Bipolar -10�00V to 0�00V R/W 042B 41068 0�00
P4.44
-AI3 High Hz Percent Bipolar -100�00% to +100�00% R/W 042C 41069 0�00
P4.45
-AI3 Mid Voltage Bipolar -10�00V to 0�00V R/W 042D 41070 –5�00
P4.46
-AI3 Mid Hz Percent Bipolar -100�00% to +100�00% R/W 042E 41071 –50�00
P4.47
-AI3 Low Voltage Bipolar -10�00V to 0�00V R/W 042F 41072 –10�00
P4.48
-AI3 Low Hz Percent Bipolar -100�00% to +100�00% R/W 0430 41073 –100�00
P4.49
reserved n/a n/a 0431 41074 n/a
P4.50
Analog Output 1 (AO1)
0: Output Frequency (Hz)
1: Frequency Command (Hz)
2: Motor Speed (Hz)
3: Output Current (A
rms
)
4: Output Voltage (V)
5: DC Bus Voltage (V)
6: Power Factor (%)
7: Power (% Rated)
8: AI1 (%)
9: AI2 (%)
10: AI3 (%)
11: As 485 AO
12: As COMM Card AO
13: Fixed Value
♦R/W 0432 41075 0
P4.51
AO1 Gain 0�0~500�0% ♦R/W 0433 41076 100�0
P4.52
AO1 Negative Value Handle
0: Absolute Value
1: 0V When Negative
2: Offset 5V = 0 Value
♦R/W 0434 41077 0
P4.53
AO1 0~20mA/4~20mA Selection
0: 0~20mA
1: 4~20mA
R/W 0435 41078 0
P4.54
Analog Output 2 (AO2)
0: Output Frequency (Hz)
1: Frequency Command (Hz)
2: Motor Speed (Hz)
3: Output Current (A
rms
)
4: Output Voltage (V)
5: DC Bus Voltage (V)
6: Power Factor (%)
7: Power (% Rated)
8: AI1 (%)
9: AI2 (%)
10: AI3 (%)
11: As 485 AO
12: As COMM Card AO
13: Fixed Value
♦R/W 0436 41079 0
P4.55
AO2 Gain 0�0~500�0% ♦R/W 0437 41080 100�0
(table continued next page)

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals