Page 4–130
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P6.11 Over-Voltage Stall Prevention
R/W 060B 41548
Range/Units (Format: 16-bit binary) Default
0: Enable Over-voltage Stall Prevention
1: Disable Over-voltage Stall Prevention
0
During deceleration, the GS4 drive DC bus voltage may exceed its Maximum Allowable Value due
to motor regeneration. When this function is enabled, the GS4 drive will stop decelerating, and
maintain a constant output frequency. The drive will resume deceleration when the voltage drops
below the factory-preset value.
DC bus voltage
Over-voltage Detection level
Output Frequency
Time
Time
NOTE: With moderate inertial loads, over-voltage during deceleration should not occur.
For applications with high inertia loads, the GS4 drive will automatically extend the
deceleration time. If deceleration time is critical for the application, a dynamic braking
resistor should be used. Set this parameter to 1 (disable) when using a dynamic braking
resistor.
Related parameters: P6.11, P6.12, P6.27

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals